SINGLE CORE, twin insulated WIRES IN VOLTAGE GRADE 1100 V conforming to IS 694 |
Nominal area of Copper Conductor |
Number / Nominal Diameter of strands |
Thickness of insulation (nominal) |
Approximate Overall Diameter of wire |
Current carrying capacity # |
Resistance (MAX)per Km @ 20 C |
In conduit / Trunking |
Unenclosed clipped directly to a surface or on cable tray |
Sq.mm |
Mm |
Mm |
Mm |
Amps |
Amps |
Ohms |
1.0 |
14/.3* |
0.7 |
2.8 |
11 |
12 |
18.10 |
1.5 |
22/.3* |
0.7 |
3.1 |
13 |
16 |
12.10 |
2.5 |
36/.3* |
0.8 |
3.8 |
18 |
22 |
7.41 |
4.0 |
56/.3* |
0.8 |
4.4 |
24 |
29 |
4.95 |
6.0 |
85/.3* |
0.8 |
5.0 |
31 |
37 |
3.30 |
Standard Color-Black, Red, Blue, Yellow & Green (for earthing). Supplied in 90 meter length in attractive carton *As per conductor Class 2 of IS:8130/1984 # As per IS 3961(part V) 1968 |
Single Core, Unsheathed Wires In Voltage Grade 1100 V |
10 |
140/.3 |
1.0 |
6.6 |
42 |
51 |
1.91 |
16 |
126/.4 |
1.0 |
7.8 |
57 |
68 |
1.21 |
25 |
196/.4 |
1.2 |
9.7 |
71 |
86 |
0.780 |
35 |
276/.4 |
1.2 |
10.9 |
91 |
110 |
0.554 |
50 |
396/.4 |
1.4 |
13.2 |
120 |
145 |
0.386 |
Standard Color-Black, Red, Blue, Yellow. Other colours on request. Supplied in 100 meter length in Coils Above sizes are as per conductor class 5 of IS:8130/1984 confirm to is 694 1990 |